Performed a refrigerant leak search after the air conditioning system was found to have insufficient cooling and abnormally low operating pressures.

System operating readings were approximately 5.2 PSIG suction pressure and 62.0 PSIG high-side pressure, with extremely high superheat of 107.8°F and subcooling of -44.1°F. These readings indicated a significant refrigerant shortage.

Inspected the indoor evaporator coil, TXV, refrigerant piping, and associated connections. Observed corrosion, oxidation, and discoloration around the evaporator assembly and refrigerant connections.

A refrigerant leak was identified at the copper suction-line connection above the indoor evaporator coil. The connection showed visible deterioration and discoloration consistent with refrigerant leakage.

The exact condition of the copper joint should be evaluated after removing the insulation. The connection may require brazing repair or replacement of the affected copper section.

The outdoor compressor was operating, and the dual-run capacitor tested within manufacturer specifications. The identified suction-line connection is the confirmed leak location associated with the system’s refrigerant loss.

Recommended Repair

Recommend cutting out the deteriorated section of copper tubing and installing a new properly sized copper section or fitting as required. The repaired connection should be brazed with nitrogen flowing through the piping to reduce internal oxidation.

After the repair, the system should be:

1. Pressure-tested with dry nitrogen.
2. Checked for leaks at the repaired connection and throughout the refrigerant circuit.
3. Evacuated to the manufacturer-required vacuum level.
4. Recharged with the correct amount of R-410A refrigerant.
5. Tested for proper operating pressures, superheat, subcooling, compressor operation, and temperature split.