Refrigerant Leak Diagnostic
Equipment: LG Multi-Zone Heat Pump
Model: LMU300HHV
Refrigerant: R-410A
Suspected Component: High-Pressure Refrigerant Sensor
Part Number: EBD62165602 (pending model revision verification)
Diagnostic Summary:
Arrived on site to inspect the LG multi-zone heat pump system due to concerns regarding low refrigerant levels and system performance.
During the inspection, identified an audible refrigerant leak coming from the high-pressure sensor area located near the refrigerant accumulator inside the outdoor condenser unit.
The leak appears to originate from the pressure sensor or its connecting fitting. Further leak testing is required to confirm the exact failure point.
Recommended Repairs:
1. Recover the remaining R-410A refrigerant using approved recovery equipment.
2. Confirm the leak location and replace the high-pressure refrigerant sensor (Part # EBD62165602), if found defective.
3. Inspect the sensor connection and surrounding refrigerant piping for additional leaks.
4. Pressure-test the repaired system using dry nitrogen.
5. Evacuate the system to the manufacturer’s required vacuum level.
6. Recharge the system with R-410A refrigerant by weight according to LG specifications.
7. Test system operation, refrigerant pressures, and overall heating and cooling performance.
Repair Status:
Refrigerant leak identified in the pressure sensor area. Repair is recommended before further operation. System repairs and refrigerant recharge have not yet been completed. Replacement part and repair estimate pending confirmation.
More jobs in Warwick: View all Warwick jobs →
Learn more: Heat pump Repair, Install & Replacement in Warwick →